Littelfuse PLM6405 Voltage Monitoring - 200-240 Volt, Double Throw, Single Pole
Normally In Stock
Code: 565376
Littelfuse PLM6405 - PLM Series – Voltage Monitor Series - 200-240 Volt - Plug-in socket - 10 A resistive @ 240 VAC 277 VAC max; 1/2 hp @ 240 VAC; 1/4 hp @ 120 VAC
Condition: New
Usually ships Same Day or Next Day$222.37
Sale Price
$185.31
Tariff Status
Tariff may apply if shipping to the United States. Tariff costs are calculated and will be displayed in the shopping cart.
Need a large quantity or a custom solution?
Add this product to your job, favorites list or request a quick quote for volume pricing and lead time information. Our team is ready to assist with any special requirements.
Related Products
Description
Littelfuse PLM6405 is an 8-pin plug-in relay with a maximum output load rating of 10 A resistive @ 240 Volts. It has a power consumption of ≤2 W and a reset time of Automatic. This relay provides surge protection according to IEEE C62.41-1991 Level B standards and has a response time of ≤200 ms for phase loss and phase reversal. This voltage detection relay is designed for 3-phase delta or WYE input with no connection to neutral. The trip delay range is fixed at 5 s and the undervoltage trip voltage is adjustable between 88% to 92% of the adjusted line voltage. The undervoltage reset voltage is +3% of the trip voltage. The voltage unbalance trip point is fixed at 4% and the voltage unbalance reset is -0.7% unbalance typical. The input phase sequence is A, B, C. The input voltage maximum is 270 V.
Specifications
Relay Throws
Double Throw
Relay Poles
Single Pole
Component
Voltage Monitoring Relay
Manufacturer
Littelfuse
Relay Mounting
Plug-In Socket
Coil Voltage Rating
200-240 Volt
Features
Quick octal 8-pin mounting
Proprietary microcontroller-based circuitry
LED diagnostics
Isolated, 10 A, SPDT output contacts
Adjustable, nominal voltage set point
Simple 3-wire connection for delta or wye systems
ASME A17.1 Rule 210.6
NEMA MG1 14:30, 14:35
IEEE C62.41-1991 Level B