ACI 141036 Q5C-CO-250P-O-X Carbon Monoxide Gas
Normally In Stock
Code: 177469
ACI 141036 Smart Sensor, Carbon Monoxide, 0-250 ppm, 3 SPDT Relays, ETL, NEMA 4X, 4-20mA, 2-10V, or Modbus RTU
Condition: New
Usually ships Same Day or Next Day$811.80
Sale Price
$676.50
Tariff Status
Tariff may apply if shipping to the United States. Tariff costs are calculated and will be displayed in the shopping cart.
Need a large quantity or a custom solution?
Add this product to your job, favorites list or request a quick quote for volume pricing and lead time information. Our team is ready to assist with any special requirements.
Description
The Q5 Series is a microprocessor based “smart” gas transmitter. It is paired with either an electrochemical gas sensor for toxic gases, or a catalytic bead sensor for combustible gases. Pre-calibrated sensors can be purchased and installed by the user, thereby reducing calibration costs and minimizing downtime. The user can select from numerous display options, including relay status, time, TWA, STEL, concentration, or nothing at all. All programming and calibration is nonproprietary and is accessed through a user selectable password which protects system integrity.
Specifications
Manufacturer
ACI
Component
Gas
(Instrument-Sensor) Type
Carbon Monoxide
(Instrument-Sensor) Span
0 - 250 PPM
Features
The B5/Q5 Toxic/Combustible Gas Detectors use various sensing technologies to detect a wide assortment of gases
These units are housed in a NEMA 4X rated plastic enclosure that will meet the most stringent applications
All models feature an internal clock, LCD Display for displaying gas concentrations and setup, LED Status Indication, integral buzzer with three user configurable relays and a number of different communication protocols for use with one of our gas controllers or your building management system
Factory calibrated sensor module replacements are available and are easily replaced in the field by removing two screws on the previous module
All units should be checked for proper functionality and calibration once the replacement sensor module is reinstalled and has had a chance to warm up
A user selectable password can be used to protect the system integrity
The Q5 can be used as a standalone gas detector or in conjunction with the Q4C, M-Controller or Q-Controllers using the proprietary RS-485 Optomux communication protocol
The B5 uses BACnet™ MSTP (RS485) protocol to communicate directly with a BAS
ACI also offers a full line of horns and strobes that can be used with the Gas detectors or building management system to alert building occupants of an alarm condition
Refer to all applicable Federal, State, Provincial and Local Health and Safety laws and regulations before using these products
The Q5/B5-GENL can be ordered to monitor specific combustible gases such as Gasoline, Ethanol, Diesel or Jet fuel
Contact ACI for specific gases.